Taihua Electronic Motor Protector AS-21N Three-phase monitoring
| ●Conform to GB/T14048.4 and many other national or industry standards. | 
| ●Three-phase electronic type, the trip level is 30. | 
| ●Possess current phase failure and overload protection functions, sensitive phase failure protection, reliable operation, and anti-interference ability Strong, set current value and overload delay are continuously adjustable; and have good inverse time characteristics and other advantages point. | 
| ●The main circuit adopts the core-through current sampling method, combined with advanced electronic (integrated circuit) circuits. | 
| ●Installation method: socket type, Din-rail type installation. | 
 
		    
			(1) Company code
(2) Motor protector
(3) Current sampling type (active type)
(4) Design serial number (specification code)
(5) B: Overload alarm (buzzer)
N: With work/test transfer switch
| Working power | AC380V、AC220V 50Hz;The allowable voltage fluctuation range is (85%-110%) Ue | 
| Adjustment method | Online current adjustment by potentiometer | 
| Output control contact | AS-21:a group of NC contactAS-22:Change over contact 1Z | 
| Reset mode | Power off reset | 
| Contact capacity | AC-12,Ue:AC380V, Ie:3A | 
| Mechanical life | 1×105 time | 
| Electrical life | 1×104 time | 
| Installation | AS-21:Device type/din railtypeAS-22:Device type | 
| Rated working current | |||
| Model | Setting current range (A) | Suitable motor power (kW) | Minimum sampling current (A) | 
| AS-21□(JD-5□) | 0.5~5 | 0.25~2.5 | ≥3 | 
| AS-21□(JD-5□) | 3~30 | 2~15 | |
| AS-21□(JD-5□) | 1~100 | 0.5~50 | |
| AS-21□(JD-5□) | 20~100 | 10~50 | |
| AS-22□(JD-6□) | 63~400 | 30~200 | 10 | 
| Comparison Table of wire core threading | ||
| Motor Power(kW) | Corresponding setting current(A) | Core-threading turns (turns) | 
| 0.25~0.5 | 0.5~1 | 12~6 | 
| 0.5~1 | 1~2 | 6~3 | 
| 1~3 | 2~6 | 3~1 | 
| ≥3 | ≥6 | 1 | 
| Overload Action Time Characteristics | ||||
| Trip level | Different current multiples and action time PT | |||
| 1.05Ie | 1.2Ie | 1.5Ie | 7.2Ie | |
| 2 | Tp:no action within 2 hours | Tp:action within 2 hours | Tp≤1min | Tp≤4s | 
| 5 | Tp≤2min | 0.5s<Tp≤5s | ||
| 10(A) | Tp≤4min | 2s<Tp≤10s | ||
| 15 | Tp≤6min | 4s<Tp≤15s | ||
| 20 | Tp≤8min | 6s<Tp≤20s | ||
| 25 | Tp≤10min | 8s<Tp≤25s | ||
| 30 | Tp≤12min | 9s<Tp≤30s | ||
Anti-time characteristic diagram of overload protection
 
		    
			AS-21/AS-21B Circuit diagram
 
		    
			AS-22 Circuit diagram
AS-21/AS-21B appearance and installation dimensions
 
		    
			 
		    
			 
		    
			AS-22 appearance and installation dimensions
 
		    
			 
		    
			 
		    
			 
		    
			 
		    
			 
        